Himoinsa cem7 коды ошибок

1. Measurements of actual power and cos phi per phase.

P O W E R :

FP: Total power factor

FP1: Power factor phase 1

FP2: Power factor phase 2

FP3: Power factor phase 3

2. Measurements of the total energy consumed in the Day, Month and Year.

E N E R G Y :

D: Daily accumulated power

M: Monthly accumulated power

A: Annual accumulated power

10.1.5 LIST OF ERRORS

*

A L A R M

*

M I N

G E N S E T

A G E

E: Alarm / A: Warning

N: Pending notification

1: Position in the list of errors

3: Number of errors

V O L T —

Fig.1

Error reading

10.1.6 TEMPERATURES BY PT100 PROBES (ONLY IF EXPANSION MODULE PT100

PROBES)

10.2 CONTROL UNIT MAINTENANCE

10.2.1 PASSWORD ENTRY

With the control unit connected, select «Menu» and confirm (V). To enter the

password using the cursor keys (+) and (-), select the number of the first digit and

confirm (V). Use the same procedure with the 4 digits.

* * * * * * *

M E N U

P a s s w o r d

0 0 0 0

Fig.1

Temperature from probes

Fig.2

Probe not detected

* * * * * * *

(APPENDIX II) CONTROL UNIT SCREENS | PAGE 68

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

INSTRUCTION MANUAL

PROFESSIONAL

DIGITAL CONTROL UNIT CEM7

loading

Summary of Contents for Himoinsa CEM7

  • Page 1
    INSTRUCTION MANUAL PROFESSIONAL DIGITAL CONTROL UNIT CEM7…
  • Page 2: Table Of Contents

    CONTENTS 1. Introduction 2. Front of the display module 3. Operating modes 4. Operation 5. CEM7 control unit inputs and outputs 6. CEM7 control unit alarms 7. Maintenance 8. Options (expansions) 9. Appendix I: parameters table 10. Appendix II. CEM7 control unit screens 11.

  • Page 3: Introduction

    1. INTRODUCTION The CEM7 control unit is a generator set power supervision and control device. The control unit consists of 2 different modules: • Display module. The display module is responsible for carrying out the information tasks regarding the status of the device and allows actions to be performed by the user;…

  • Page 4
    The measurements module provides the following electrical signal characteristics, • Tariff change warning both those generated and those from the network itself: • Tariff change (CEM7 + CEA7CC2) • Phase-neutral voltage • Start up disabling • Phase-to-phase voltage •…
  • Page 5
    • Timer device • Telesignal device • CCJ1939 device • Repetitive display • Telecontrol device • Announcement panel device • CAN/USB • CAN/232 + MODEM LINE • CAN/232 + MODEM GSM • CAN/232 + MODEM GSM/GPS POSITIONING • CAN/232 + MODEM GPRS HG FLEET MANAGER •…
  • Page 6: Front Of The Display Module

    The display module has a backlit display and various LEDs for monitoring the status of the control unit. It also has keys that allow the user to control and program the control unit. Fig.1 CEM7 display module Fig.2 CEM7P display module FRONT OF THE DISPLAY MODULE | PAGE 6…

  • Page 7
    1. Backlit display 4 lines by 20 digits. 2.1.2 CONTROL UNIT COMMAND BUTTONS Engine start button (only in manual mode) NOTE The display goes into low power mode (backlight off) after 10 minutes have Controls the start up with a single push. passed without any keystroke.
  • Page 8
    These LEDs only appear active when the switching control unit is connected. Alternator status Off: Stopped engine or engine running Start up option due to Network Voltage Failure (CEM7 + CEA7CC2) battery charging without voltage in the battery charging The M and G symbols on the front of the control unit only appear activated when alternator the switching control unit is connected.
  • Page 9
    2.3 PASSWORDS The CEM7 control unit has 2 levels of 4-digit password to protect against unauthorized access. The different levels of access are as follows: • User (default password: 1111). User level access allows the operator to access the main menu of the CEM7 control unit.
  • Page 10: Operating Modes

    START and STOP keys respectively. Pressing the START key initiates the engine starting procedure (without deactivating the network contactor CEM7 + CEA7CC2). Pressing the STOP key initiates the engine stopping procedure with cooling; a second press of the STOP key causes the engine to stop immediately without waiting for the cooling time.

  • Page 11
    3.3 MODE LOCKING FUNCTION Pressing the Auto or Man keys for 5 seconds activates the locking of the mode. This control unit state is indicated by the flashing of the mode key currently active. To deactivate the mode lock and allow normal operation of the control unit, press the key associated to the active mode for 5 seconds.
  • Page 12: Operation

    1. Start delay. Once activation conditions are detected, it is possible to program a time delay (Times table, parameter 3) before continuing the engine start up procedure only in automatic (CEM7 + CEA7CC2 or CEM7 + AE) 2. Preheating of the motor (PR). The control unit activates preheating output (PR) for the programmed time (Times table, parameter 4).

  • Page 13
    4. Starting the motor (ARR). For a maximum time (Times table, parameter 5), 4.1.2 GAS ENGINE the start output of the measurements module is activated while waiting to detect 1. Checking the engine gas train (PR). The process of checking the gas train at least one of the programmed start conditions.
  • Page 14
    7. Generator stabilisation. Once any start condition is detected, the control unit PRACTICAL EXAMPLE OF A START OPERATION waits for a fixed time for stabilization of the generator signal before monitoring the quality of the generator signal. NOTE 8. Nominal condition. After achieving engine stabilisation, verification of the Before starting the start cycle it is advisable to ensure the genset’s main circuit generator signal is performed.
  • Page 15
    Fig.2 Fig.4 Once it has been detected that the engine is running the LED switches on ( ), If during the start cycle, the engine started condition is not detected after 5 this indicates the end of the start cycle and the START button turns off. (3) seconds, the ARR output deactivates and the corresponding LED turns off ).
  • Page 16
    NOTE • Pickup frequency (Regulations table, parameter 21). The engine is considered stopped when the pickup frequency is below the start The display shows the engine status screen, where the engine status is displayed up threshold (Threshold table, parameter 22). To activate the pickup during the start up operation.
  • Page 17
    PRACTICAL EXAMPLE OF A STOP OPERATION NOTE Before starting the stop cycle it is advisable to ensure the genset’s main circuit breaker is in the off position (OFF). The genset stop can be performed in various ways: 1. Manual: Pressing the STOP button once. To perform a stop with cooling cycle. 2.
  • Page 18
    4.3 FUEL TRANSFER PUMP It is possible to activate the fuel transfer pump of the CEM7 control unit by associating its operation with the BT relay of the measurements module (Regulations table, parameter 4). Once the fuel transfer pump option is enabled, the operating mode is then set (Regulations table, parameter 1): 1.
  • Page 19
    4.5 BATTERY CHARGING ALTERNATOR managing the fuel transfer pump and fuel level alarm) a calibration of the tank The battery charging alternator is connected to the CEM7 control unit via the gauge should be performed. This requires access to the minimum and maximum gauge level parameters (Measurements table, parameters 12 and 13).
  • Page 20
    From the firmware versions of control units: Display 3.20 / Measurements 2.50 4.6 START/STOP KEY 4.8 ELECTRONIC PROTECTION The start/stop key in the ON position causes power to be supplied to the CEM7 control unit’s electronic devices (measurements module and display module). DESCRIPTION The start/stop key in the OFF position causes a controlled stop if it is running;…
  • Page 21
    4.9 MOTORPUMP MODE 4.10 GENSET IN RESERVE DESCRIPTION DESCRIPTION The motorpump mode configures the CEM 7 control unit to display only engine The genset in reserve function allows the operation of several generator sets in measurements, hiding generator set voltage measurements. This configuration the same installation.
  • Page 22: Cem7 Control Unit Inputs And Outputs

    15-24) which requires that the value of the input is stable over a time interval. Also, all of the CEM7 control unit’s inputs can be configured to be active with contact closed to earth or be inactive with contact closed to earth (Regulations table parameters 5 to 15).

  • Page 23
    Detection of an active output is indicated by the following characters: 5.1 DIGITAL INPUTS • OUT 1. Alarm active (AL) The CEM7 control unit’s measurements module has 5 digital inputs with • OUT 2. Motor started (MA) operation that is already preset.
  • Page 24
    TEST SIGNAL (TEST) The CEM7 control unit’s measurements module has 5 digital inputs with This function is only managed in automatic mode of the CEM7 control unit with operation that can be programmed. The programmable inputs can be configured the motorised circuit breaker option.
  • Page 25
    5.3 ANALOGUE INPUTS There are 2 additional programmable alarms available (Settings table, parameters The CEM7 control unit has 5 analogue inputs for measuring the engine operation 22 and 23) that can be associated with any of the programmable inputs and values.
  • Page 26
    52 to 54) when the fuel level is detected to be below this limit. The CEM7 control unit allows you to add 8 analogue temperature inputs to the PT100 sensor through the expansion of up to 2 CCPT100 devices. 2 maximum…
  • Page 27
    PREHEATING OUTPUT. (PR). POWER OUTPUT FUEL TRANSFER PUMP/HEATING/ELECTRONIC PROTECTION OUTPUT (BT). The preheating output (PR) of the CEM7 control unit is an output connected to a RELAY OUTPUT high power shortable driver (70 A) which regulates the heating process of the The fuel transfer pump/heating output (BT) of the CEM7 control unit is a relay engine’s spark plugs during the starting process.
  • Page 28
    STARTED ENGINE OUTPUT (MA). DIGITAL OUTPUT The alarm output (AL) is responsible for communicating the different states of The started engine output (MA) of the CEM7 control unit is activated when any the CEM7 control unit. The AL output simultaneously activates the flashing of the started engine condition is detected and remains active while the engine is Reset key LED and display module buzzer of the CEM7 control unit.
  • Page 29
    (Thresholds table, is detected (Thresholds table, parameter 32) during a set time (Times table, parameter 35). Both with the activation and deactivation of the load demand CEM7 CONTROL UNIT INPUTS AND OUTPUTS | PAGE 29…
  • Page 30
    The output remains active if the correct operation of the generator set’s control system is verified. The CEM7 control unit has 4 additional programmable outputs installed in the Second Zero Suppression expansion, the operation of which can be configured to indicate certain states (Settings table, parameters 18 to 21).
  • Page 31: Cem7 Control Unit Alarms

    6. CEM7 CONTROL UNIT ALARMS The CEM7 control unit has a list of alarms, the operation of which can be configured so that actions are performed or so that they are shown on the display module screen. The CEM7 control unit distinguishes between errors that cause the engine to stop (alarms) and errors do not cause the engine to stop (warnings).

  • Page 32
    2. Pressing the RESET button eliminates the acoustic warning. The RESET LED remains lit and the type of alarm is shown on the display (which stops flashing). Ex: Alarm active “EN” High Water Temperature. CEM7 CONTROL UNIT ALARMS | PAGE 32…
  • Page 33
    2. Pressing the RESET button eliminates the acoustic warning. The RESET LED TEMPERATURE remains LIT and the type of warning is shown on the display (which stops flashing). Active warning “AN”. NOTICE HIGH WATER TEMPERATURE Fig.3 Fig.2 CEM7 CONTROL UNIT ALARMS | PAGE 33…
  • Page 34
    1. Upon detection of an alarm or warning, the control unit produces an acoustic Fig.5 signal, the LED of the RESET button and the display flashes and the alarm digital output (AL) is activated. Fig.4 CEM7 CONTROL UNIT ALARMS | PAGE 34…
  • Page 35
    LEDS Aux1 and Aux2. Low oil pressure by sensor Lit LED Notice Not for engine Not for engine Low fuel level by sensor Lit LED Notice Unexpected stop Stop failure CEM7 CONTROL UNIT ALARMS | PAGE 35…
  • Page 36
    All alarms except those which are non-programmable, can be configured as LOW OIL PRESSURE follows: The CEM7 control unit’s low oil pressure alarm is associated with the digital To be activated: input specifically for the low oil pressure (BPA) or errors detected by the engine’s •…
  • Page 37
    LOW WATER LEVEL measurements module (stops engine) ensuring the engine shutdown is set as The CEM7 control unit’s low water level alarm is associated with the digital input stop via de-energisation (Regulations table, parameter 18) independently of the specifically for the low water level (NA) or errors detected by the engine’s CIU control unit’s electronics.
  • Page 38
    FUEL RESERVE The CEM7 control unit’s under speed alarm is associated with the measurement The CEM7 control unit’s fuel reserve alarm is associated with the digital input of the engine flywheel ring gear’s rotation speed or through the J1939 channel of specifically provided for the fuel reserve (RC).
  • Page 39
    MAXIMUM GENSET FREQUENCY GENSET VOLTAGE ASYMMETRY The CEM7 control unit’s maximum genset frequency alarm is associated with the The CEM7 control unit’s genset voltage asymmetry alarm is associated with the condition that the frequency generated by the genset is above the maximum fact that the difference between any two RMS voltages between genset voltage frequency limit set (Thresholds table, parameter 5).
  • Page 40
    LOW OIL PRESSURE BY SENSOR The CEM7 control unit’s low oil pressure by sensor alarm is associated with the LOW BATTERY VOLTAGE analogue input for the oil pressure (T). The low oil pressure by sensor alarm is…
  • Page 41
    LOW FUEL LEVEL BY SENSOR The CEM7 control unit’s high battery voltage alarm is activated when the battery The CEM7 control unit’s low fuel level by sensor alarm is associated with the voltage measured is above a set limit (Thresholds table, parameter 36).
  • Page 42
    SHORT CIRCUIT The CEM7 control unit’s minimum genset frequency alarm is associated with the The CEM7 control unit’s short circuit alarm is associated with the condition that condition that the frequency generated by the genset is below the minimum the measurement of the RMS current is above the maximum short circuit limit frequency limit set (Thresholds table, parameter 6).
  • Page 43
    GENSET SIGNAL FAILURE detected. The CEM7 control unit’s genset failure signal alarm is generated if no genset voltage is detected during any phase while the engine is running. PROGRAMMABLE ALARM 2 Detection of the genset failure signal alarm is set by default (Alarms table, parameter 76) to be activated under nominal engine conditions.
  • Page 44
    PROGRAMMABLE ALARM 5 PROGRAMMABLE ALARM 3 The CEM7 control unit’s programmable alarm 5 is activated associating the The CEM7 control unit’s programmable alarm 3 is activated associating the operating mode of the programmable alarms (Settings table, parameter 23) to operating mode of the programmable alarms (Settings table, parameter 15) to…
  • Page 45
    (Alarms table, parameter 131) to perform no action (warning). The CEM7 control unit’s high temperature alarm for PT100 level 2 probes 1 to 4 is associated to the analogue inputs for PT100 temperature of the analogue input expansion.
  • Page 46
    IDMT ALARM EXAMPLE CALCULATION OF THE IDMT CURVE TIME CONSTANT (T) The CEM7 control unit’s IDMT alarm is associated to the measurement of the For a genset current (I) with a value of 110% of the nominal value, the desired genset current.
  • Page 47: Maintenance

    7. MAINTENANCE 7.1 OPERATION COUNTERS The CEM7 control unit records different accumulated readings related to control unit operation. The counters that record the control unit are: • Total operating hours counter. The control unit records the number of hours that the genset engine has been operating. The total operating hours counter cannot be reset to zero.

  • Page 48
    7.2 MAINTENANCE COUNTERS 7.3 LIST OF PREVIOUS ERRORS The CEM7 control unit has 3 programmable counters that are loaded for a certain The CEM7 control unit keeps a record of the detected alarms saving the status time which decreases while the engine is detected as running. The maintenance…
  • Page 49
    For display modules (CEM7 and CEA7), the Master display module The CEM7 control unit has a series of temperature and pressure sensors curves must have the same ID as the associated measurement module.
  • Page 50
    4. The first programmable fuel curve corresponds to the generator set’s main fuel sensor. This curve is used for gauges with nonlinear responses that need more than 2 points for programming. If the CEM7 control unit detects a curve programmed in the first fuel curve, it cancels the parameters corresponding to the linear calibration of the generator set’s main gauge (Measurements table, parameters 12 and 13 ).
  • Page 51: Options (Expansions

    8. OPTIONS (EXPANSIONS) New functions can be added to the CEM7 control unit using the CAN bus connection via expansion modules. 8.1 DISPLAY SCREEN (REPETITIVE) The control units CEA7 and CEM7 allow display screens to be added to the installation. This device displays the current status of the control unit, and if it is in automatic mode, can control the functioning of the genset.

  • Page 52
    • Energy counters (day, month, year) 3. It will be slightly elevated so that it can be accessed easily. The maximum timer limit is 5 daily programs. The CEM7 control unit must be in automatic mode in order to manage the incorporated programming.
  • Page 53
    INPUT/OUTPUT screen if it is detected that the J1939 extension is installed or option CEM7J. Both the CEM7J option and the CEM7 control unit with the expansion CCJ1939 can monitor the following engine operating parameters depending on the…
  • Page 54
    16 LEDs each one of connection using TCP/IP connections. The CCLan device allows the following: which can be associated with one of the following states of the CEM7 control unit: • Remote monitoring and control via a TCP/IP connection as well as •…
  • Page 55
    8.11 ANALOGUE INPUTS EXPANSION PT100 The CEM7 control unit allows the connection of a CPT100 device for measuring up to 4 temperature probes for display and management of the generator set alarms. 8.12 PRECISION GAUGE EXPANSION The CEM7 control unit allows the connection of a precision gauge device for measuring the level in fuel tanks.
  • Page 56: Appendix I: Parameters Table

    9. APPENDIX I: PARAMETERS TABLE The CEM7 control unit allows 3 levels of access for settings. To modify any of the CEM7 control unit’s parameters validation is required by entering the correspond- ing password. The 3 levels of access are: 1.

  • Page 57
    Table 1 Times Table Default Default Parameter Description Range Parameter Description Range value value Number of Starts 1..10 Filtering of the ENT5 input 1.0’’ 0.0’’.. 120.0’’ Time between Starts Filtering of the ENT1 input 1.0’’ 0.0’’.. 120.0’’ Period between starts during which all the outputs 5’’…
  • Page 58
    Table 3 Regulations Table Default Default Parameter Description Range Parameter Description Range value value 0-Off Phase voltage as starting condition 1-Manual 0- No consultation Fuel transfer pump operating mode 2-Automatic Alternator voltage as starting condition 1 3-Control unit mode/ 1- Motor started Combined mode 2- Motor stopped PICK-UP input as starting condition.
  • Page 59
    Table 4 Table 6 Analogue sensors. Related to parameter 29 in the Regulations table External start-up configuration table. Related to parameter 31 in the regulations table Value Coolant temperature Oil pressure Oil temperature Value Fitting property 9 10 11 12 13 14 15 VDO: 323-803-001-008 VDO: 360-081-030-009 ѵ…
  • Page 60
    Table 8 Default Parameter PSW Description Range Alarms Table value Starting speed (PICK UP) 1000 rpm 300-1000 Parameter PSW Description Default value Range Engine flywheel teeth 0-300 0- Not checked 1- Always checked Low fuel level 0..30 2- When starting Management alarm 0 3- From start condition Low oil pressure threshold…
  • Page 61
    Parameter PSW Description Default value Range Parameter PSW Description Default value Range Management alarm 10 Mode alarm 19 0..2 0..4 Asymmetry Management alarm 20 0..4 Filter alarm 10 8” 0”…255” Minimum Unit Voltage Mode alarm 10 0..2 Filter alarm 20 8”…
  • Page 62
    Parameter PSW Description Default value Range Parameter PSW Description Default value Range Management alarm extension 2 Mode alarm probe 3 0..2 Programmable alarm 5 0..4 Management alarm probe 4 (from version PHG6/7 v250) Temperature probe 4 0..4 Delay alarm extension 2 0’…
  • Page 63
    Table 9 Default Parameter PSW Description Range Settings Table (I/O) value Input associated to CKG mode Default Parameter PSW Description Range value Input associated to EJP1 mode 0- Not programmed Input associated to EJP2 mode 2- BPA (option CEM7J) 0- Not programmed Input associated to IA mode 3- ATA (option CEM7J) 1- RC Input…
  • Page 64
    Table 12 Parameter PSW Description Default value Range Parameters clearance selector Table 0- Not programmed Default Input associated to AL4 mode Parameter PSW Description Range 2- BPA (option CEM7J) value 3- ATA (option CEM7J) 0- Three-phase without 4- NA (option CEM7J) neutral 5- ENT4 Input associated to AL5 mode…
  • Page 65
    Table 13 Table 14 Table J1939 Screen Table Parameter PSW Description Default value Range Parameter PSW Description Default value Range SCANIA EMS 0: Buzzer enabled Inhibition of buzzer VOLVO EDC4 1: Buzzer disabled VOLVO EMS2 VOLVO EMS1 0: Enable PD activation in IVECO CURSOR PD inhibition in inputs/outputs I/O menu…
  • Page 66: Appendix Ii. Cem7 Control Unit Screens

    10. APPENDIX II. CEM7 CONTROL UNIT SCREENS 10.1 CONTROL UNIT STATUS The status of the CEM7 control unit is shown on the display, allowing access to different display options using the up and down navigation keys. 10.1.1 GENERATOR MEASUREMENT SCREENS 1.

  • Page 67
    RPM, H operating hours, NC fuel level, DI battery charging alternator voltage, TM Fig.1 engine temperature, VB battery voltage, PA oil pressure and, either AA auxiliary CEM7 + CEA7CC2 temperature or NC2 fuel level in auxiliary tank. G E N S E T :…
  • Page 68
    1. Measurements of actual power and cos phi per phase. 10.1.6 TEMPERATURES BY PT100 PROBES (ONLY IF EXPANSION MODULE PT100 PROBES) P O W E R : FP: Total power factor Fig.1 Temperature from probes FP1: Power factor phase 1 FP2: Power factor phase 2 FP3: Power factor phase 3 2.
  • Page 69
    10.2.2 MAIN MENU 1. INPUTS AND OUTPUTS DISPLAY The main menu screen gives access to the different menus, to enter each menu select it with the cursor (+) (-) and confirm (v): I N P U T S / O U T P U T S 1.
  • Page 70
    The second screen displaying J1939 measurements is available for firmware A N A L O G U E I N P U T S versions 3.36 and higher for genset and automatic display modules. NC: Fuel level PA: Oil pressure TM: Engine temperature AA: Auxiliary analogue IM: Intake Manifold Temperature…
  • Page 71
    * * * *  F a i l e d S t a r t s The scheduling in the CEM7 control unit is conditioned so that the option of a T o t a l  timer is enabled. The scheduling is carried out via the fifth option of the maintenance menu.
  • Page 72
    * * * * * S C H E D U L E S * * * * *  S u n d a y  * * * * * M o n d a y * * * * * …
  • Page 73
     6. DATE AND TIME * * * L A N G U A G E * * *  Select the hour and confirm (V), adjust the time (+) (-) and confirm (V), adjust the minutes (+) (-) and confirm (V), adjust the seconds (+) (-) and confirm (V). 8.
  • Page 74
     10. SYNCHRONIZATION  See Second Zero expansion manual. Confirm key (v)  11. HARMONICS  The control unit performs a calculation of the different voltage and current  harmonics. The information shown is: • Spectrum graphic in frequencies Confirm key (v) …
  • Page 75
    10.3 CONTROL UNIT PROGRAMMING * * * * M E A S U R E M E N T S * * * *  To enter each menu select it with the cursor (+) (-), and confirm (v):  …
  • Page 76
    10.3.3 CUSTOMISING THE MANUFACTURER’S SCREEN Programming the response curves of the sensors entering decreasing resistance value points. For curve 1 associated with temperature sensors, positive and From the programming texts option of the control unit it is possible to customise negative values temperature are permitted;…
  • Page 77
    10.3.6 LIST OF ERRORS J1939 From the J1939 option it is possible to display the active and passive past errors stored in the engine’s electronic configuration. E N G I N E H I S T O R Y  …
  • Page 78
    10.3.7 LIST OF STARTS (ONLY EXPANSION CCJ1939) 10.4 ACCESS TO MENUS From the J1939 option it is possible to display the starts carried out from the CEACC2 MENU Associ- J1939 extension in standalone mode. External ated Inputs/Outputs    …
  • Page 79: Appendix Iii: Dimensions, Wiring And Mechanical Parts

    11. APPENDIX III: DIMENSIONS, WIRING AND MECHANICAL PARTS 11.1 MEASUREMENTS MODULE PHG7 VOLTAGE FREE DIGITAL RELAY OUTPUT OUTPUTS DIGITAL OUTPUTS VOLTAGE FREE ANALOGUE RELAY OUTPUT INPUTS PICK-UP DIGITAL CURRENT INPUTS NETWORK CANBUS VOLTAGE POWER SUPPLY GENSET VOLTAGE Fig.1 Measurements module wiring (APPENDIX III) DIMENSIONS, WIRING AND MECHANICAL PARTS | PAGE 79…

  • Page 80
    WARNING The equipment must be isolated or disconnected before performing this wiring, there is a risk of danger. Fig.2 Measurements module wiring 2 FUEL TRANSFER NETWORK GENSET PUMP OR HEATING CONTACTOR CONTACTOR ACTIVATION CONTACTOR Fig.5 Measurements module wiring 5 Fig.3 Measurements module wiring 3 EMERGENCY OVERLOAD AND…
  • Page 81
    Table 1 SIGNAL DESCRIPTION TYPE Characteristics Measurements module wiring PHG7 SAL3 Output 3 Output PNP digital output SIGNAL DESCRIPTION TYPE Characteristics SETA Emergency stop button Output NPN digital input 8÷36V Positive battery terminal Power supply Control unit supply voltage from 8 to 36V Configurable stop Output PNP digital output of power…
  • Page 82
    Table 2 Electrical Characteristics Mini- Typi- Maxi- Symbol Parameter Conditions Unit POWER SUPPLY (TERMINALS 8÷36V, –BAT, +BAT) 8÷36V Power supply of the control unit +BAT Power supply of the outputs Supply current 8÷36V=12V Supply current 8÷36V=24V Power consumption CAN BUS (TERMINALS CANS, CANL, CANH) Input voltage in CANH and CANL Baud rate Kbps…
  • Page 83
    11.2 DISPLAY MODULE CEM7 Mini- Typi- Maxi- Symbol Parameter Conditions Unit PNP OUTPUTS (TERMINALS D+, AL, MA, SAL1, SAL2, SAL3) Output voltage +BAT Output current Output resistance D+ Ω PNP POWER OUTPUTS (TERMINALS PC, PR, ARR) Output voltage +BAT Output current T = ∞…
  • Page 84
    Table 4 Electrical characteristics Mini- Typi- Maxi- Symbol Parameter Conditions Unit POWER SUPPLY (TERMINALS 8÷36 V, –BAT, +BAT) 8÷36 V Power supply of the control unit +BAT Power supply of the outputs 8÷36 V = Supply current 12 V 8÷36 V = Supply current 24 V Power consumption…
  • Page 85
    11.3 MEASUREMENTS MODULE PHG7J Mini- Typi- Maxi- Symbol Parameter Conditions Unit Input frequency = 12 VAC 3600 VOLTAGE FREE DIGITAL RELAY OUTPUT OUTPUTS ANALOGUE INPUTS (TERMINALS NC, P, T, AnC=TC, DI, GND) Input voltage Fuel level resistance Ω DIGITAL Pressure resistance Ω…
  • Page 86
    Fig.2 Measurements module wiring section 1 OVERLOAD AND EMERGENCY SHORT CIRCUIT STOP CONTACTOR To power the plate it is recommended that a cable be used with a cross-section of 1 mm POWER OUTPUTS MAC: 40 A Fig.5 Measurements module wiring section 4 To carry out the wiring a cable with a cross-section of 2.5 mm must be used for +BAT, ARR, PR and PC connections.
  • Page 87
    Table 5 Signal Description Type Characteristics Measurements module wiring PHG7J SETA Emergency stop button Output Low-level digital input active Signal Description Type Characteristics Configurable stop Output High-level power digital output active Control unit supply voltage from 8 to 8÷36 V Positive battery terminal Power supply Preheating…
  • Page 88
    Table 6 Electrical Characteristics Mini- Typi- Maxi- Mini- Typi- Maxi- Symbol Parameter Conditions Unit Symbol Parameter Conditions Unit POWER SUPPLY (TERMINALS 8÷36V, –BAT, +BAT) ANALOGUE INPUTS (TERMINALS NC, P, T, AnC, DI, GND) 8÷36 V Power supply of the control unit Input voltage +BAT Power supply of the outputs…
  • Page 89
    11.4 DISPLAY MODULE: CEM7.1 POWER SUPPLY Fig.1 Measurements module display 1 Fig.2 Measurements module display 1 To power the plate it is recommended that a cable be used with a cross-section of 1 mm Fig.7 Measurements module dimensions. (APPENDIX III) DIMENSIONS, WIRING AND MECHANICAL PARTS | PAGE 89…
  • Page 90
    Table 7 Display module wiring CEM7.1 SIGNAL DESCRIPTION TYPE CHARACTERISTICS 8÷36V Positive battery terminal Power supply Control unit supply voltage from 8 to 36V Negative battery -BAT Power supply Control unit supply negative terminal Manual Input PNP digital input AUTO…
  • Page 91
    For proper protection of the equipment, the following elements must be installed in the control panel: Fuses Amps General Positive Power Digital Automatic Control Unit CEM7 Phase U Phase V Phase W Differential Relay + Tripping Coil Battery Charger…
  • Page 92: Appendix Iv: Can Communications

    12. APPENDIX IV: CAN COMMUNICATIONS 12.1 INTRODUCTION The CAN BUS, is an industrial bus characterized by great strength and reliability and ensures proper communication between the devices in noisy environments. Devices with CAN controller can be integrated into an industrial automation and control system.

  • Page 93
    NOTE Table 2 The existing impedance must be measured when all the equipment is no longer working Characteristics of the cable depending on the number of nodes or does not have physical access to the network. For more information, please see the ISO 11898 specification and the different notes that apply in this respect.
  • Page 94
    12.4 WIRING DIAGRAMS MANUAL SWITCHING MEASUREMENTS MEASUREMENTS MEASUREMENTS DISPLAY DISPLAY Fig.3 Manual / automatic control unit CCrs MANUAL SWITCHING MEASUREMENTS MEASUREMENTS Fig.6 Manual control unit + switching + CCrs DISPLAY DISPLAY Fig.4 Manual control unit + switching MEASUREMENTS CCrs DISPLAY Fig.5 Manual / automatic control unit + CCrs option (APPENDIX IV) CAN COMMUNICATIONS | PAGE 94…
  • Page 95: Appendix V: Calibration Of The Control Unit

    13. APPENDIX V: CALIBRATION OF THE CONTROL UNIT The CEx7 control unit allows calibration adjustments to be made to the voltage measurements of the genset and network (only control units CEA7 and CE- A7CC2). For this purpose, it is enabled in the Parameters menu Measurements …

  • Page 96
    Using the keys the voltage between phase and neutral measured by the con-  trol unit is adjusted to match the actual value. * * * * M E A S U R E M E N T S * * * * …
  • Page 97: Appendix Vi: Expanding Inputs

    14. APPENDIX VI: EXPANDING INPUTS 15. APPENDIX VII: COMMUNICATIONS FAILURE The CEx7 control unit allows you to add digital inputs, analogue inputs (0-10 V, The user interface of the CEx7 control unit displays the text COMMUNICATIONS 4-2 0mA and resistant) and PT100 by connecting input expansion module devic- FAILURE when it cannot establish communication with the PHG7 control module.

  • Page 98
    Fax +34 968 19 12 17 | Export Fax +34 968 33 43 03 www.himoinsa.com HIMOINSA reserves the right to modify any characteristic without prior notice. Illustrations may include optional equipment and/or accessories. Non contractual images. The technical information described in this manual corresponds to the information available at the time of printing.

This manual is also suitable for:

Cem7.2

Specifications:

1495/1495524-cem7.pdf file (28 Mar 2023)

Accompanying Data:

Himoinsa CEM7 Control Unit PDF Instruction Manual (Updated: Tuesday 28th of March 2023 07:09:52 PM)

Rating: 4.7 (rated by 75 users)

Compatible devices: N-9390, AP3156FVG, Allen-Bradley 1756-HIST1G, FPBA-01, TLC5510, Ultramis TX91, InFlow 76X Series, K8006.

Recommended Documentation:

Text Version of Himoinsa CEM7 Instruction Manual

(Ocr-Read Summary of Contents, UPD: 28 March 2023)

  • 11, Himoinsa CEM7 OPERATING MODES | PAGE 11 3.3 MODE LOCKING FUNCTION Pressing the Auto or Man keys for 5 seconds activates the locking of the mode. This control unit state is indicated by the ashing of the mode key currently active. To deactivate the mode lock and allow normal operation of th…

  • 37, Himoinsa CEM7 CEM7 CONTROL UNIT ALARMS | PAGE 37 STARTING FAILURE The CEM7 control unit’s starting failure alarm is generated if the number of consecutive retries (Times table, parameter 1) and failures is exceeded during engine start. Between each start attempt a programmable delay is observed …

  • 90, (APPENDIX III) DIMENSIONS, WIRING AND MECHANICAL PARTS | PAGE 90 Fig.3 Display module dimensions Table 7 Display module wiring CEM7.1 SIGNAL DESCRIPTION TYPE CHARACTERISTICS 8÷36V Positive battery terminal Power supply Control unit supply voltage from 8 to 36V -BAT Negative battery terminal Power supply Control un…

  • 82, (APPENDIX III) DIMENSIONS, WIRING AND MECHANICAL PARTS | PAGE 82 Fig.7 Measurements module dimensions Table 2 Electrical Characteristics Symbol Parameter Conditions Mini- mum Typi- cal Maxi- mum Unit POWER SUPPLY (TERMINALS 8÷36V, –BAT, +BAT) 8÷36V Power s…

  • 83, (APPENDIX III) DIMENSIONS, WIRING AND MECHANICAL PARTS | PAGE 83 Symbol Parameter Conditions Mini- mum Typi- cal Maxi- mum Unit PNP OUTPUTS (TERMINALS D+, AL, MA, SAL1, SAL2, SAL3) V O Output voltage +BAT V I O Output current 1 A R D+ Output resistance D+ 47 Ω PNP POWER OUTPUTS (TERMINALS PC, PR, ARR)…

  • 43, Himoinsa CEM7 CEM7 CONTROL UNIT ALARMS | PAGE 43 PROGRAMMABLE ALARM 1 The CEM7 control unit’s programmable alarm 1 is activated associating the operating mode of the programmable alarms (Settings table, parameter 13) to one of the general purpose digital inputs (ENT1, ENT2, ENT3, ENT…

  • 48, MAINTENANCE | PAGE 48 Display. The remaining operating time before a maintenance alarm is generated is displayed in the Counters menu->Maint.#1 in hours and minutes. Notification. To report the maintenance alarm, it must be programmed from the Counters menuMaint.#1 p…

  • 45, CEM7 CONTROL UNIT ALARMS | PAGE 45 ENGINE J1939 COMMUNICATION The engine J1939 communication alarm veries proper communication between the CEM7J control unit and the engine via the J1939 bus. This alarm is only available for CEM7J control units which have the J1…

  • 77, (APPENDIX II) CONTROL UNIT SCREENS | PAGE 77 * ON 1 / 4 Fig.5 Flashing code * ON Fig.6 Error status ON Fig.7 Error counter ON Fig.8 List of errors 10.3.6 LIST OF ERRORS J1939 From the J1939 option it is possible to display the active and passive past errors stored in …

  • 49, MAINTENANCE | PAGE 49 7.6 PROGRAMMING ANALOGUE SENSORS CURVE The CEM7 control unit has a series of temperature and pressure sensors curves programmed for different VDO capsule types (model 323-803-001-008 for temperature and model 360-081-030-009 for pressure) and engines (VOLVO, JCB, SCANIA, Y…

  • Himoinsa CEM7 User Manual

  • Himoinsa CEM7 User Guide

  • Himoinsa CEM7 PDF Manual

  • Himoinsa CEM7 Owner’s Manuals

Recommended Instructions: BRC1D517, TR1200, Ultimate Timers

  • Mitsubishi Electric 800 Series

    800A800FR-A860 (600V CLASS SPECIFICATION INVERTER)INSTRUCTION MANUAL (STARTUP)FR-A860-00027-00450-N6FR-A860-00680-04420Thank you for choosing this Mitsubishi Electric Inverter.This Instruction Manual and the enclosed CD-ROM give handling information and precautions for use of thisproduct.Do not use this product until you have a full knowledge of the equipment, sa …

    800 Series 25

  • Ewellix SCU

    SCU Brief instructions for initializationINSTALLATION INSTRUCTIONSSafety, Operating manual, TroubleshootingBefore start-up, please read the operating instructions for the SCU control unit carefully and pay special attention to the safety notes. The relevant notes an operating manual can be found at https://medialibrary.ewellix.com/asset/16223.www.ewellix.com/en/ …

    SCU 2

  • Lunt Solar Systems PC-USB

    1 Instruction Manual PC-USB Electronic Control unit with USB for one LUNT Pressure-Tuner system The PC-USB is a microprocessor controlled pressure control system for the LUNT Pressure-Tuner (PT) tuning technique. All existing LUNT Pressure-Tuner systems can be retrofitted to the PC-USB controller via an included adapter. The controller can be manually operated, or vi …

    PC-USB 4

  • Thermon Terminator ECM-P-XP

    1725 II 2 GD Ex eb mb [ib]ib I IC T4, Ex tb IIIC T135°C SIRA 12ATEX5239XIP66-60°C ≤ Ta ≤ + 55°CIECEx SI R 12.0103X Ex eb mb [ib]ib IIC T4, Ex tb IIIC T135°CPN 27673Do not open while energized. See installation instructions. Terminator ECM For use as an adjustable electronic control moduleThe Heat Tracing Specialists®Terminator TM ECM-P-XPElectron …

    Terminator ECM-P-XP 8

Additional Information:

Popular Right Now:

Operating Impressions, Questions and Answers:

Table of Contents for Himoinsa CEM7:

  • (APPENDIX II) CONTROL UNIT SCREENS | PAGE 67 10.1.3 CONTROL UNIT STATUS SCREEN 1. Status of the programmable inputs GENSET: STOPPED START INHIBITED Fig.1 CEM7 + CEA7CC2 GENSET: STOPPED START INHIBITED Fig.2 Status of the programmable inputs IA: Start inhibited AE: External start CKG: Conrmation of genset contactor CKR: Conrmation of network contactor K-: Relay activation loading T: Test function F: Forced operation function JP1: EJP1 function JP2: EJP2 function 10.1.4 POWER AND ENERGY

  • (APPENDIX III) DIMENSIONS, WIRING AND MECHANICAL PARTS | PAGE 82 Fig.7 Measurements module dimensions Table 2 Electrical Characteristics Symbol Parameter Conditions Mini- mum Typi- cal Maxi- mum Unit POWER SUPPLY (TERMINALS 8÷36V, –BAT, +BAT) 8÷36V Power supply of the control unit 8 36 VDC +BAT Power supply of the outputs 8 36 VDC I BAT Supply current 8÷36V=12V 100 mA I BAT Supply current 8÷36V=24V 50 mA P BAT Power consumption 1.2 W CAN BUS (TERMINALS CANS, CANL, CANH) V IN Input voltage

  • (APPENDIX III) DIMENSIONS, WIRING AND MECHANICAL PARTS | PAGE 88 Symbol Parameter Conditions Mini- mum Typi- cal Maxi- mum Unit ANALOGUE INPUTS (TERMINALS NC, P, T, AnC, DI, GND) V I Input voltage 5 V R NC Fuel level resistance 0 400 Ω R P Pressure resistance 0 200 Ω R T Water temperature resistance 0 4000 Ω R TC Oil temperature resistance 0 4000 Ω D I Alternator voltage 0 40 V PNP OUTPUTS (TERMINALS D+, AL, MA, SAL1, SAL2, SAL3) V O Output voltage +BAT V I O Output current 1 A R D+ Output resistance D+ 47 Ω PNP POWER OUTPUTS (TERMINALS PC, PR, ARR) V O Output

  • (APPENDIX II) CONTROL UNIT SCREENS | PAGE 68 10.1.6 TEMPERATURES BY PT100 PROBES (ONLY IF EXPANSION MODULE PT100 PROBES) Fig.1 Temperature from probes Fig.2 Probe not detected 10.2 CONTROL UNIT MAINTENANCE 10.2.1 PASSWORD ENTRY With the control unit connected, select «Menu» and conrm (V). To enter the password using the cursor keys (+) and (-), select the number of the rst digit and conrm (V). Use the same procedure with the 4 digits. * * * * * * * MENU * * * * * * * Password 0 0 0 0 1. Measurements of actual power and cos phi per p

  • “AN” WARNING THAT NEEDS TO BE RESET, DOES NOT CAUSE THE ENGINE TO STOP 1. Upon detection of an alarm or warning, the control unit produces an acoustic signal, the LED of the RESET button and the display ashes and the alarm digital output (AL) is activated. Fig.1 2. Pressing the RESET button eliminates the acoustic warning. The RESET LED remains LIT and the type of warning is shown on the display (which s

  • CEM7 CONTROL UNIT INPUTS AND OUTPUTS | PAGE 25 VERIFICATION OF GAS RAMP (S1 AND S2) The input congured to perform the gas train verication function (Settings table, parameter 25) is used in gas engines (Regulations table, parameter 18, value 4) to complete the testing process of the gas ramp and start the engine start up process. 5.3 ANALOGUE INPUTS The CEM7 control unit has 5 analogue inputs for measuring the engine operation values. These analogue inputs characterize the operation of the engine to display its status and produce alarms if necessary

  • CEM7 CONTROL UNIT ALARMS | PAGE 45 ENGINE J1939 COMMUNICATION The engine J1939 communication alarm veries proper communication between the CEM7J control unit and the engine via the J1939 bus. This alarm is only available for CEM7J control units which have the J1939 option installed. Detection of the engine J1939 communication alarm is set by default (Alarms table, parameter 144) to be act

  • CEM7 CONTROL UNIT INPUTS AND OUTPUTS | PAGE 29 parameter 26). The programmable output congured as programmed output for dummy load is deactivated when higher genset power consumption than the programmed threshold is detected (Thresholds table, parameter 33) during a set time (Times table, parameter 26). As a condition for enabling the dummy load output, the engine must be in a stabilized state. NOTE From the rmware versions of control units: Display 3.20 / Measurements 2.50 PROGRAMME

  • (APPENDIX I) PARAMETERS TABLE | PAGE 64 Table 12 Parameters clearance selector Table Parameter PSW Description Default value Range 1 2 Signal type clearance 1 1 0- Three-phase without neutral 1- Three-phase 2- Two-phase 3- Single-phase 4- Delta with neutral 5- Delta without neutral 6- Two-phase selector 2 2 Maximum Unit Voltage clearance 1 440V 3 2 Minimum Unit Voltage clearance 1 360V 4 2 Maximum generator current clearance 1 1000A 5 2 Short circu

  • PRACTICAL EXAMPLE OF A START OPERATION NOTE Before starting the start cycle it is advisable to ensure the genset’s main circuit breaker is in the off position (OFF). OPERATION By pressing the START button the start cycle is initiated and is indicated by the START button’s LED switching on. At the same time if the motor has a preheating plug the PR output is activated, with the corresponding LED switching on ( ), for the programmed time. (1) Fig.1 Once this time has elapsed the PR output is deactivated, and the correspondi

  • INTRODUCTION | PAGE 5 • Timer device • Telesignal device • CCJ1939 device • Repetitive display • Telecontrol device • Announcement panel device • CAN/USB • CAN/232 + MODEM LINE • CAN/232 + MODEM GSM • CAN/232 + MODEM GSM/GPS POSITIONING • CAN/232 + MODEM GPRS HG FLEET MANAGER • CAN/232 + MODEM GPRS/GPS HG FLEET MANAGER • CAN/485 (MODBus) • CAN/LAN • CAN/LAN (MODBUS IP) • CAN/LAN HG FLEET MANAGER • Second Zero Suppressor • PT100 temperature probes expansion • ATS panel with CEC7 contro

  • (APPENDIX II) CONTROL UNIT SCREENS | PAGE 66 10. APPENDIX II. CEM7 CONTROL UNIT SCREENS 10.1 CONTROL UNIT STATUS The status of the CEM7 control unit is shown on the display, allowing access to different display options using the up and down navigation keys. 10.1.1 GENERATOR MEASUREMENT SCREENS 1. Measurements of voltage between the various phases and neutral, the phase currents and frequency. GENERATOR: 2. Measurements of

  • Fig.2 Once it has been detected that the engine is running the LED switches on ( ), this indicates the end of the start cycle and the START button turns off. (3) Fig.3 The LED corresponding to the battery charging alternator voltage ( ) switches on when the voltage provided by the alternator exceeds the voltage threshold set by default. (4) Fig.4 If during the start cycle, the engine started condition is not detected after 5 seconds, the ARR output deactivates and the corresponding LED turns off ( ). Subsequently the control u

  • INSTRUCTION MANUAL PROFESSIONAL DIGITAL CONTROL UNIT CEM7

  • (APPENDIX I) PARAMETERS TABLE | PAGE 60 Table 8 Alarms Table Parameter PSW Description Default value Range 1 3 Management alarm 0 High Water Temperature 1 0- Not checked 1- Always checked 2- When starting 3- From start condition (Stabilised) 4- From nominal condition (In operation) 2 3 Delay alarm 0 0 ’’ 0”…255” 3 3 Mode alarm 0 1 0- Not for engine 1- For engine 2- For engine with cooling 4 3 Management alarm 1 Low oil pressure 4 0..4 5 3 Delay alarm 1 15’’ 0”…255” 6 3 Mode alarm 1 1

  • (APPENDIX III) DIMENSIONS, WIRING AND MECHANICAL PARTS | PAGE 87 Signal Description Type Characteristics SETA Emergency stop button Output Low-level digital input active PC Congurable stop Output High-level power digital output active PR Preheating Output High-level power digital output active ARR Starting Output High-level power digital output active SAL4 Output 4 Output High-level power digital output active +BAT Positive battery terminal Power supply Digital outputs supply voltage SCC Overload and short circuit Output Overload and short circuit relay, C contact S

Questions, Opinions and Exploitation Impressions:

You can ask a question, express your opinion or share our experience of Himoinsa CEM7 device using right now.

Sugiéranos cómo mejorar StudyLib

(Para quejas, use

otra forma
)

Tu correo electrónico

Ingrese si desea recibir respuesta

Nos califica

1

2

3

4

5

Возможно, вам также будет интересно:

  • Hikvision ошибка создания файла
  • Hikvision ошибка пароля пользователя на камере
  • Hikvision ошибка обновления прошивки
  • Hikvision ошибка кода opensdk string error 510004
  • Hikvision ошибка кода hcnetsdk dll

  • Понравилась статья? Поделить с друзьями:
    0 0 голоса
    Рейтинг статьи
    Подписаться
    Уведомить о
    guest

    0 комментариев
    Старые
    Новые Популярные
    Межтекстовые Отзывы
    Посмотреть все комментарии